What Is the Difference Between Equal Percentage and Linear Control Valve Characteristics?

2026-09-17

1. What Are Inherent and Installed Characteristics?

The inherent characteristic of a control valve is the relationship between the valve opening percentage and the flow capacity (Cv) when the pressure drop across the valve is held constant. The installed characteristic is the relationship when the valve is installed in a system where the pressure drop varies with flow. This distinction is critical because the installed characteristic determines the actual control performance. For a linear valve, the inherent characteristic is a straight line: 50 percent open gives 50 percent of maximum Cv. For an equal percentage valve, the inherent characteristic is exponential: each equal increment of stem travel produces an equal percentage change in the existing flow. At 50 percent open, an equal percentage valve may provide only 15 to 20 percent of maximum Cv. 

Micro Flow Single Seat Control Valve

The table below compares the inherent Cv values for the two characteristics.

Valve opening (%) Linear Cv (% of max) Equal percentage Cv (% of max)
10 10 2.0
20 20 3.5
30 30 6.0
40 40 10.0
50 50 17.0
60 60 28.0
70 70 46.0
80 80 68.0
90 90 85.0
100 100 100

Zhejiang Lozose Intelligent Control Instrument Co., Ltd. manufactures Conventional Series Control Valve units with both linear and equal percentage trim options. Our factory tests the inherent characteristic of every valve on a flow bench to verify that it matches the published curve.


2. How Does System Pressure Drop Affect the Installed Characteristic?

The installed characteristic is determined by the ratio of the pressure drop across the valve at full flow to the total system pressure drop. This ratio is called the valve authority or the pressure drop ratio. When the valve authority is high (the valve accounts for most of the system pressure drop), the installed characteristic is close to the inherent characteristic. When the valve authority is low (the valve accounts for a small fraction of the total pressure drop), the installed characteristic becomes distorted. A linear valve in a low-authority system will have an installed characteristic that is closer to equal percentage. An equal percentage valve in a low-authority system will have an installed characteristic that is closer to linear. The table below shows the installed characteristic for different valve authorities.

Valve authority Installed characteristic (linear inherent) Installed characteristic (equal % inherent)
High (0.7 – 1.0) Nearly linear Strongly equal percentage
Medium (0.3 – 0.7) Moderately distorted Moderately distorted
Low (0.1 – 0.3) Approaches equal percentage Approaches linear

This is why the selection of the valve characteristic cannot be made in isolation. It must be based on the system design. In our factory, we work with process engineers to calculate the valve authority before recommending a characteristic. We provide a valve sizing and selection service that includes the installed characteristic calculation.


3. What Is the Practical Selection Criteria for Equal Percentage vs Linear?

The selection criteria for a Conventional Series Control Valve characteristic depend on the process dynamics. The following rules of thumb are widely used in the industry. Use an equal percentage characteristic when the process is a temperature control loop, a pressure control loop with a wide load range, or any loop where the pressure drop across the valve decreases as the flow increases. Use a linear characteristic when the process is a level control loop, a flow control loop with a constant pressure drop, or a loop where the pressure drop across the valve is relatively constant. The table below summarizes the typical applications for each characteristic.

Process application Recommended characteristic Reason
Heat exchanger temperature control Equal percentage Wide load range, variable pressure drop
Pressure reduction station Equal percentage Variable downstream pressure
Level control in a surge tank Linear Constant head, self-regulating process
Flow control with a fixed restriction Linear Constant pressure drop across valve
Reactor feed control Equal percentage Wide range of feed rates

When the process characteristics are uncertain, an equal percentage valve is often the safer choice because it provides better control at low flow and is more forgiving of oversized valves. A linear valve that is oversized will have poor resolution at low flow and may cause cycling.


4. How Does the Control Loop Tuning Differ Between the Two Characteristics?

The installed characteristic affects the loop gain, which is the product of the valve gain, the process gain, and the controller gain. If the installed characteristic is highly nonlinear, the loop gain will vary with the operating point, which can cause instability at one operating point and sluggish response at another. A well-designed loop will have a relatively constant loop gain. This is achieved by selecting a valve characteristic that compensates for the nonlinearity of the process. For example, if the process gain decreases as the load increases, an equal percentage valve (whose gain increases with flow) can compensate and keep the loop gain constant. If the process gain is constant, a linear valve is the better choice. In our factory, we provide support for loop tuning. We can calculate the installed gain and recommend controller settings for your specific process.

Practical tuning tip: If you are experiencing oscillation at low flow and sluggish response at high flow with a linear valve, switching to an equal percentage trim may solve the problem without changing the controller settings. This is one of the most common valve-related tuning issues in process plants.


Frequently Asked Questions About Control Valve Characteristics

Question 1: Can I change the characteristic of an existing control valve without replacing the entire valve?
Answer: In many cases, yes. The characteristic of a control valve is determined by the shape of the plug and the cage. If your Conventional Series Control Valve has a replaceable trim, you can change from a linear plug to an equal percentage plug (or vice versa) by replacing the plug and cage assembly. This is a common retrofit in process plants where the original characteristic was not optimal. The cost of a trim replacement is typically 30 to 50 percent of the cost of a new valve. In our factory, we supply replacement trim kits for all of our valve models. We also provide the flow characteristic data for each trim option so you can verify the expected performance.
Question 2: What happens if I install an equal percentage valve in a system where a linear valve was specified?
Answer: The result depends on the valve authority. In a high-authority system, the equal percentage valve will provide very low flow at small openings and will reach maximum flow only near 100 percent open. This may cause the process to be difficult to control at low flow rates because the valve is too sensitive. In a low-authority system, the installed characteristic may actually approach linear, so the performance may be acceptable. However, the safest approach is to match the valve characteristic to the system design. If you are unsure, we recommend using an equal percentage valve because it is more forgiving of oversizing. In our factory, we can calculate the installed characteristic for your specific system and advise on the best choice.
Question 3: How do I verify the characteristic of a control valve after installation?
Answer: The most reliable method is to record the flow rate and valve position at several operating points. Plot the flow percentage against the valve position percentage. For a linear valve, the plot should be a straight line. For an equal percentage valve, the plot should be an exponential curve. If the plot does not match the expected characteristic, there may be a problem with the valve trim, the actuator calibration, or the system pressure drop. In our factory, we perform this test on every valve before shipment. We can also perform a field verification test if you have a flow meter and a positioner with feedback. This test takes about 2 hours and can identify installation issues that may affect performance.

Summary for Process Control Engineers

The difference between equal percentage and linear control valve characteristics is not just a matter of trim shape. It is a matter of how the valve interacts with the system pressure drop and the process gain. The correct selection requires an understanding of the valve authority, the process dynamics, and the control loop tuning. Equal percentage valves are generally preferred for temperature and pressure control loops with wide load ranges. Linear valves are preferred for level and flow control loops with constant pressure drops. Zhejiang Lozose Intelligent Control Instrument Co., Ltd. has been manufacturing Conventional Series Control Valve units for over 18 years and provides full engineering support for valve selection and loop tuning.

Lozose manufactures Conventional Series Control Valve units with linear, equal percentage, and modified parabolic trim options. We provide valve sizing calculations, installed characteristic analysis, and actuator selection support.

Need help selecting the right control valve characteristic for your process? Contact Zhejiang Lozose Intelligent Control Instrument Co., Ltd. for a free valve sizing consultation. We will calculate the installed characteristic and recommend the optimal trim for your application.
Previous:No News
Next:No News

Leave Your Message

  • Click Refresh verification code